THERMAL OVERLOAD RELAY - TZ | |||
![]() |
Prevents overheating of motor windings. Can be used with motors that have built-in temperature-dependent resistors (PTC) in windings. Choice of automatic or manual reset.
Basic features: -standard supply voltage: 230Vac; 24Vac/dc -consumption: 2VA -cut off threshold: when the PTC resistance reaches 3000ohm (+ / -10%) -restart: when resistance drops to 2000ohm (+ / -10%) -contact rating: 5A/220Vac -operating temperature range: -10 / +55 C |
![]() |
|
LEVEL SWITCH - RZP | |||
![]() |
It is used to detect the presence of conductive liquids in metal or tanks of insulating material. It can be used to automatically refill the reservoir or to protect the pump from dry running. With jumper 5-6 on the front panel you can choose whether the relay will be on when the liquid level reaches the probe S1 (pump protection) or to be off when S1 is reached (filling a tank). Basic features: power supply: 230Vac consumption: 2VA contact rating: 5A/230Vac mounting: rail 35mm |
![]() |
|
UNDERVOLTAGE/OVERVOLTAGE RELAY - NR | |||
![]() |
Detection of too high or too low line voltage. Control voltage also serves to power up relay. Basic features: |
![]() |
|
THREE PHASE UNDERVOLTAGE/OVERVOLTAGE RELAY NR3 | |||
![]() |
Independently adjustable threshold: |
||
PHASE SYMETRY AND UNDERVOLTAGE CONTROL - NF03 | |||
![]() |
Main purpose is protection of three-phase motors and other consumers from line voltage failure and asymmetry. Control voltage also serves to power up relay. Basic features:
|
||
PHASE SYMETRY AND UNDERVOLTAGE CONTROL WITH TIME DELAY - NFT03 | |||
![]() |
Adjustable:
-asymmetry 5-30% -time delay 0-10s -automatic reset -option: manual reset Fixed: -under voltage:175V
|
||
PHASE SEQUENCE, SYMETRY AND UNDERVOLTAGE CONTROL - NF04 | |||
![]() |
Detection of the correct phase sequence
Adjustable: -asymmetry 5-30% -under voltage: 160... 220Vac -standard: automatic reset -option: manual reset:
|
||
PHASE SEQUENCE, SYMETRY AND UNDERVOLTAGE CONTROL WITH TIME DELAY - NFT04 | |||
![]() |
Detection of the correct phase sequence |
||
RELAY FOR POWER FACTOR CORECTION - COS FI | |||
|
Measure angle between phase voltage and current and has the ability to correct power factor in three steps by adding capacitor banks. A simple solution for small business sites and consumers who have no reactive power variations in a wide range.
| ||
DIMENSIONAL DRAWING | |||
![]() |
A=22.5mm NR3,NF03,NF04,NFT03,NFT04, TZ A=37mm...RZP,COS FI |
NR |
![]() |
In order to rationalize production and continuous improvement of product quality changes are possible in the appearance and characteristics of actual devices compared to this catalog. | |||
ABOUT US PRODUCTS |